Powerware 9125 Two-in-One UPS
2500/3000 VA
User’s Guide

®

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
Оглавление инструкции
  • Страница 1 из 79
    Powerware® 9125 Two-in-One UPS 2500/3000 VA User’s Guide
  • Страница 2 из 79
    Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a
  • Страница 3 из 79
    Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition S EU Directives: 73/23/EEC, Council Directive on equipment designed for use
  • Страница 4 из 79
    Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your
  • Страница 5 из 79
    Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Installation . . . . .
  • Страница 6 из 79
    TABLE OF CONTENTS 7 UPS Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 UPS and Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
  • Страница 7 из 79
    Chapter 1 Introduction The Powerware® 9125 uninterruptible power system (UPS) protects your sensitive electronic equipment from the most common power problems including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switching transients,
  • Страница 8 из 79
    INTRODUCTION S Start-on-battery capability for powering up the UPS even if utility power is not available. S Hot-swappable batteries that simplify maintenance by allowing you to replace batteries safely without powering down the critical load. S Emergency shutdown control through the remote
  • Страница 9 из 79
    Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for
  • Страница 10 из 79
    SAFETY WARNINGS CAUTION S Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from
  • Страница 11 из 79
    SAFETY WARNINGS ADVARSEL S Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding. De korrekte forholdsregler bør overholdes. S Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. S Skaf
  • Страница 12 из 79
    SAFETY WARNINGS OPGELET S Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op. S De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. S Nooit
  • Страница 13 из 79
    SAFETY WARNINGS Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES DANGER! Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN
  • Страница 14 из 79
    SAFETY WARNINGS Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAREN Dieses Handbuch enthält wichtige Hinweise, welche Sie bei der Installation und Wartung die USV beachten sollten. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem Gerät arbeiten. Bewaren Sie das Handbuch
  • Страница 15 из 79
    SAFETY WARNINGS VORSICHT! S Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten. Wartungsarbeiten sollten nur von qualifiziertem Fachpersonal, welches sich mit dieser Art von Batterien
  • Страница 16 из 79
    SAFETY WARNINGS ATTENZIONE S Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da alta corrente dovuta a corto circuito. Osservare le apposite istruzioni. S Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle
  • Страница 17 из 79
    SAFETY WARNINGS Regulamentos de Segurança INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES CUIDADO A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA
  • Страница 18 из 79
    SAFETY WARNINGS Предупреждения по мерам безопасности ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ ОПАСНО В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться
  • Страница 19 из 79
    SAFETY WARNINGS Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES PELIGRO Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR
  • Страница 20 из 79
    SAFETY WARNINGS Säkerhetsföreskrifter VIKTIGA SÄKERHETSFÖRESKRIFTER SPARA DESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER FARA Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service. Det finns inga
  • Страница 21 из 79
    Chapter 3 Installation This section explains: S Equipment inspection S UPS internal battery connection S UPS setup and installation S Extended Battery Module (EBM) installation S Remote emergency power-off (REPO) installation S UPS rear panels Inspecting the Equipment If any equipment has been
  • Страница 22 из 79
    INSTALLATION Connecting the UPS Internal Battery To ensure proper battery operation before installing the UPS: 1. Verify that the UPS is off and unplugged. 2. Remove the UPS front cover by pulling on both ends (see Figure 2). Figure 2. Removing the UPS Front Cover 3. Connect the internal battery
  • Страница 23 из 79
    INSTALLATION Rack-Mount Setup The UPS can be installed in 19-inch racks and needs only 2U of valuable rack space. CAUTION The UPS and EBM are heavy (see page 61). A minimum of two people are required to lift the cabinets into the rack. NOTE Mounting rails are required for each UPS and EBM cabinet.
  • Страница 24 из 79
    INSTALLATION NOTE The EBMs must be installed below the UPS as shown in Figure 6. 5. Slide the UPS and any optional EBMs into the rack. 6. Secure the cabinets to the rack according to the rail kit instructions. UPS Optional EBMs Figure 6. Rack-Mount UPS with EBMs 7. If installing optional EBMs,
  • Страница 25 из 79
    INSTALLATION Figure 7. Installing UPS Pedestals (for One Cabinet) 4. Carefully position the cabinet upright with the air vents at the top (see Figure 8). 5. Continue to “Plug-Receptacle UPS Installation” on page 25 or “Hardwired UPS Installation” on page 27 to complete the installation. Air Vents
  • Страница 26 из 79
    INSTALLATION 7. Place the EBM cabinet upside down so that the right end of the cabinet is accessible (see Figure 10). Figure 10. Installing EBM Pedestals 8. Align the pedestals with the screw holes on the end of the EBM cabinet. Secure the pedestals with the screws provided in the accessory kit. 9.
  • Страница 27 из 79
    INSTALLATION NOTE Pedestals are required for installations with one or two cabinets. Joining brackets are required for installations with two or more cabinets. Air Vents Figure 12. Tower Setup with Three Cabinets 10. Align each joining bracket with the adjacent corner screw holes and secure with
  • Страница 28 из 79
    INSTALLATION Extended Battery Module Installation CAUTION A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly. To install the optional EBMs: 1. If installing an EBM
  • Страница 29 из 79
    INSTALLATION 4. E/EH UPS models have a battery connector cover that must be removed before installing the EBM(s). Remove the cover from the rear panel as shown in Figure 15. NOTE Keep the battery connector cover and screws for future use. If the UPS is stored or used without an EBM, the battery
  • Страница 30 из 79
    INSTALLATION 6. Plug the EBM cable into the UPS battery connector (see Figure 17). 7. Attach the fixed cover plate (supplied in the accessory kit) to the EBM cable as shown in Figure 17. UPS Battery Connector UPS EBM Cable EBM Cable with Fixed Cover Plate EBM EBM Battery Connector with Cover EBM
  • Страница 31 из 79
    INSTALLATION Plug-Receptacle UPS Installation NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage may occur to your equipment and void your warranty. Figure 18 shows a typical installation only. See “UPS Rear Panels” on page 33 for the rear panel of each model. To
  • Страница 32 из 79
    INSTALLATION 4. For 208/230V models only. Plug the detachable UPS power cord into the input connector on the UPS rear panel. 5. Plug the UPS power cord into a power outlet. All front panel indicators flash briefly and the UPS conducts a indicator flashes, self-test. When the self-test is complete,
  • Страница 33 из 79
    INSTALLATION Hardwired UPS Installation WARNING Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Risk of electrical shock. CAUTION S For UPS models with hardwired outputs, overcurrent protection for the output AC circuit(s) is to be
  • Страница 34 из 79
    INSTALLATION To hardwire the UPS: 1. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable. 2. Switch off utility power at the distribution point where the UPS will be connected. Be absolutely sure there is no
  • Страница 35 из 79
    INSTALLATION 5. Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the end of each incoming wire. 6. Connect the input and ground wires to the input terminal block according to Figure 22 and Table 1. 7. Connect the
  • Страница 36 из 79
    INSTALLATION 10. Switch the main utility breaker on. All front panel indicators flash briefly and the UPS conducts a indicator flashes, self-test. When the self-test is complete, the indicating the UPS is in Standby mode with the equipment offline. If or indicator flashes, see page 65. the μ
  • Страница 37 из 79
    INSTALLATION Remote Emergency Power-off Installation The Powerware 9125 includes a REPO port that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location. The REPO feature shuts down the protected equipment immediately and does not follow the orderly
  • Страница 38 из 79
    INSTALLATION 3. Connect isolated, normally-closed, dry contacts (rated to handle 60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum) across the REPO device to Pin 1 and Pin 2 (see Figure 24). Use stranded, non-shielded wiring, size 0.75 mm2–0.5 mm2 (18–20 AWG). NOTE A separate contact must
  • Страница 39 из 79
    INSTALLATION UPS Rear Panels This section shows the rear panels of the Powerware 9125 models. REPO Port Battery Connector Fuse Holder Communication Port Network Transient Protector X-Slot Communication Bay Two 5-20 Receptacles Circuit Protector Two 5-15 Receptacles 5-30 Receptacle Power Cord with
  • Страница 40 из 79
    INSTALLATION REPO Port Terminal Block Communication Port Network Transient Protector X-Slot Communication Bay Battery Connector Figure 28. 2500/3000 VA, 208–240V Hardwired Rear Panel REPO Port Terminal Block Communication Port Network Transient Protector X-Slot Communication Bay Battery Connector
  • Страница 41 из 79
    Chapter 4 Operation This section describes: S Turning the UPS on and off S Starting the UPS on battery S Initiating the self-test S Operating modes Turning the UPS On After the UPS is connected to utility power, it conducts a self-test and enters Standby mode. To turn on the UPS, press the On
  • Страница 42 из 79
    OPERATION Turning the UPS Off NOTE Pressing the Off down immediately. button while the UPS is in Battery mode causes the UPS to shut To turn off the UPS: 1. Prepare your equipment for shutdown. 2. Press and hold the Off button for approximately three seconds. The UPS transfers to Standby mode (if
  • Страница 43 из 79
    OPERATION Operating Modes Powerware 9125’s front panel indicates the UPS status through the UPS indicators. Figure 30 shows the UPS front panel indicators and controls. Normal Mode Indicator Alarm Indicators (see page 63) Bar Graph Indicators Battery Mode Indicator Bypass Mode Indicator Indicator
  • Страница 44 из 79
    OPERATION Normal Mode μ During Normal mode, the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the protected equipment (see Figure 31). The UPS monitors and charges the batteries as needed and provides power protection to your equipment. <10%
  • Страница 45 из 79
    OPERATION Battery Mode When the UPS is operating during a power outage, the alarm beeps once per second and the + --- indicator illuminates. The front panel displays the approximate percentage of battery capacity remaining (see Figure 32). When utility power returns, the UPS transfers to Normal
  • Страница 46 из 79
    OPERATION Bypass Mode In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power. Battery mode is not available; however, the utility power continues to be passively filtered by the UPS. The indicator illuminates. The UPS transfers to Bypass mode when: S
  • Страница 47 из 79
    Chapter 5 Configuration When the UPS is in Configuration mode, the bar graph indicators represent the configuration options. Use the control buttons button) to modify the UPS configuration. Figure 33 (On button and shows the LEDs and Table 2 explains the corresponding options. NOTE The UPS can be
  • Страница 48 из 79
    CONFIGURATION Configuration Mode Indicators 1 & 4 3 Press the Test/Alarm Reset button to select an option. Press and hold the On and Test/Alarm Reset buttons simultaneously to toggle between Configuration and Operation modes. Test/Alarm Reset Button On Button 2 Press the On button to scroll to the
  • Страница 49 из 79
    CONFIGURATION Table 2. Configuration Mode LEDs and Options Configuration Mode LEDs Option LED Status Explanation 120, 208, or 230V Nominal Input Voltage On (default) Nominal input voltage is one of the following: S 120V for U models S 208V for EU/EUH and G/GH models S 230V for E/EH models All other
  • Страница 50 из 79
    CONFIGURATION 44 EATON Powerware® 9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D www.powerware.com
  • Страница 51 из 79
    Chapter 6 Additional UPS Features This section describes: S X-Slot cards S Network transient protector S Load segments X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 9125 is factory-installed with a
  • Страница 52 из 79
    ADDITIONAL UPS FEATURES X-Slot Communication Bay (Single-Port Card shown) ConnectUPS-X Web/SNMP Card Relay Interface Card Modbus Card Multi-Server Card USB Card Figure 34. Optional X-Slot Cards Single-Port Card The Powerware 9125 is factory-installed with a Single-Port Card, enabling connection to
  • Страница 53 из 79
    ADDITIONAL UPS FEATURES Table 3. Communication Port Pin Assignment Pin Number Signal Name Function Direction from the UPS 1 Low Batt Low Battery relay contact; 20 mA, 30 Vdc contact rating Out 2 TxD Transmit to external device Out 3 RxD Receive from external device In 4 DTR PnP (Plug and Play) from
  • Страница 54 из 79
    ADDITIONAL UPS FEATURES On-Bypass Disabled NORM On-Bypass Enabled AS/400 On-Bypass Relay Jumper (J3) Figure 37. On-Bypass Relay Jumper 3. To prevent electrostatic discharge (ESD), place one hand on a metal surface such as the UPS rear panel. Align the Single-Port Card with the slot guides and slide
  • Страница 55 из 79
    ADDITIONAL UPS FEATURES Network Transient Protector The network transient protector, shown in Figure 38, is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a single RJ-45 (10BaseT) network connector. Low voltage models can also accommodate an RJ-11 telephone
  • Страница 56 из 79
    ADDITIONAL UPS FEATURES Load Segments Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other
  • Страница 57 из 79
    Chapter 7 UPS Maintenance This section explains how to: S Care for the UPS and batteries S Replace the batteries S Test new batteries S Recycle used batteries or UPS UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very
  • Страница 58 из 79
    UPS MAINTENANCE When to Replace Batteries When the indicator flashes, the batteries may need replacing. button for three Conduct a self-test by pressing and holding the indicator should seconds. After the five-second test is complete, the indicator turn off (it may take a few seconds to turn off).
  • Страница 59 из 79
    UPS MAINTENANCE How to Replace UPS Internal Batteries CAUTION Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS. To replace the UPS internal batteries: 1. Remove the UPS front cover by pulling on both ends (see Figure 41). Figure 41.
  • Страница 60 из 79
    UPS MAINTENANCE 4. Unscrew and set aside the battery retaining bracket (see Figure 43). Battery Retaining Bracket Figure 43. Removing the Battery Retaining Bracket 5. Pull the battery trays out onto a flat, stable surface (see Figure 44). See “Recycling the Used Battery or UPS” on page 57 for
  • Страница 61 из 79
    UPS MAINTENANCE How to Replace Extended Battery Modules CAUTION The Extended Battery Module (EBM) is heavy (see page 61). A minimum of two people are required to lift the EBM when it is replaced. To replace the Extended Battery Modules (EBMs): 1. Unplug the EBM cable from the UPS. NOTE For 230V
  • Страница 62 из 79
    UPS MAINTENANCE Joining Brackets EBM Battery Connectors UPS Battery Connector EBM Cables Figure 45. EBM Connections (120V UPS Model Shown) Testing New Batteries Press and hold the button for three seconds to initiate a self-test. indicator should turn off After the five-second test is complete, the
  • Страница 63 из 79
    UPS MAINTENANCE Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS. WARNING S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required.
  • Страница 64 из 79
    UPS MAINTENANCE 58 EATON Powerware® 9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D www.powerware.com
  • Страница 65 из 79
    Chapter 8 Specifications This section provides the following specifications: S Model list S Electrical input and output S Weights and dimensions S Environmental and safety S Battery Table 4. Model Specifications Model Number Power Levels (Rated at Nominal Inputs) PW9125-2500U 2500 VA, 1750W
  • Страница 66 из 79
    SPECIFICATIONS Table 5. Power Connections Output Connections Model M d l Input Connection I tC ti PW9125-2500U PW9125-3000U Load Segment 1 Load Segment 2 6-ft, 5 30P tt h d 6 ft 5-30P attached power cord d (2) 5-15R and (2) 5 20R 5 15R d 5-20R (1) 5 30R output cord 5-30R t t d PW9125-2500EU
  • Страница 67 из 79
    SPECIFICATIONS Table 7. Weights and Dimensions UPS 43.2 × 60.7 × 8.9 cm 17.0” × 23.9” × 3.5” (2U) Weights 43.2 × 60.7 × 8.9 cm 17.0” × 23.9” × 3.5” (2U) 37 kg (81.5 lb) Dimensions (WxDxH) Extended Battery Module 42.5 kg (93 lb) Table 8. Environmental and Safety 120V Models 208V Models Operating
  • Страница 68 из 79
    SPECIFICATIONS Table 9. Battery UPS Configuration (6) 12V, 9 Ah internal batteries EBM Configuration PW9125 72 EBM: (12) 12V, 9 Ah (2 strings of 6 batteries in parallel) Type Sealed, maintenance-free, valve-regulated, lead-acid Charging Internal battery: approximately 3 hours to 90% usable capacity
  • Страница 69 из 79
    Chapter 9 Troubleshooting This section explains: S UPS alarms and conditions S How to silence an alarm S Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems. Use Table 11 to determine and resolve the UPS alarms and
  • Страница 70 из 79
    TROUBLESHOOTING Table 11. Troubleshooting Guide Alarm or Condition Possible Cause Action The power cord is not connected correctly. Check the power cord connections. The wall outlet is faulty. Have a qualified electrician test and repair the outlet. The main utility breaker is off. Verify that the
  • Страница 71 из 79
    TROUBLESHOOTING Alarm or Condition Possible Cause Action Shutdown imminent. Prepare equipment for shutdown. The UPS is in Bypass mode. The equipment is transferred to utility power; however, the utility power continues to be passively filtered by the UPS. Check for one of the following alarms:
  • Страница 72 из 79
    TROUBLESHOOTING Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative. United States: Canada: All other countries: 1-800-356-5737 or 1-919-870-3149
  • Страница 73 из 79
    Chapter 10 Warranty Two-Year Limited Warranty (US and Canada) Powerware UPS Models: 3105, 3110, 3115, 9104, 9120, 9125, and FERRUPS® up to 3.1 kVA WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a Delaware Corporation company (“Company”).
  • Страница 74 из 79
    WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the
  • Страница 75 из 79
    WARRANTY COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for
  • Страница 76 из 79
    WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the
  • Страница 77 из 79
    WARRANTY OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with
  • Страница 78 из 79
    WARRANTY WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User’s equipment does not include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including