11 Приложение
VEGAPULS 62 с опускной трубой • Протокол Modbus и Levelmaster
41363-R
U-121123
Параметр
Length
Code/Data
Slave ID
1 Byte
Run Indicator Status
1 Byte
FC43 Sub 14, Read Device Identification
Этим кодом функции может запрашиваться Device Identification.
Request:
Параметр
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Object ID
1 Byte
0x00 to 0xFF
Response:
Параметр
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Confirmity Level
1 Byte
0x01, 0x02, 0x03, 0x81, 0x82, 0x83
More follows
1 Byte
00/FF
Next Object ID
1 Byte
Object ID number
Number of Objects
1 Byte
List of Object ID
1 Byte
List of Object length
1 Byte
List of Object value
1 Byte
Depending on the Object ID
11.5 Команды Levelmaster
VEGAPULS 62 может также подключаться к удаленным терминалам с протоколом
Levelmaster. Протокол Levelmaster часто обозначается как протокол "Siemens" или "Tank".
RTU
Protocol
ABB Totalflow
Levelmaster
Kimray DACC 2000/3000
Levelmaster
Thermo Electron Autopilot
Levelmaster
Параметры для шинной связи
VEGAPULS 62 имеет следующие значения по умолчанию:
Параметр
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8