Note (1) Thermostat operation is performed in A, B Block. When compressor and indoor fan stop by thermostat operation within 12 minutes from start, temperature

check is performed by operating indoor fan at speed 1 for 20 seconds before finishing 12 minutes and allowing decision of next operation block.

(3)

DRY operation

After finishing start up operation described in (2) above, thermal dry operation is performed at 8 minutes intervals, according to the

difference between room temperature and thermostat setting temperature as shown below.

Beside, 1 cycle of this operating time consists of 8 minutes, 7 cycle operation is performed then.

D Block

C Block

B Block

A Block

4.8 Outline of dehumidifying operation

(1)

Choose the appropriate operation block area by the difference between room temperature and thermostat

setting temperature as shown below.

¡

Operation block area

–2

0

+3

Room temp.

– Setting temp.(deg)

(2)

Start up operation

ON

OFF

OFF

0

3

6

9

12

ON

OFF

OFF

0

12

Compressor
and
outdoor fan

Set fan speed

Indoor fan

Start

Temperature check

Start

Temperature check

Compressor
and
outdoor fan

Set fan speed

Indoor fan

Operation block decision

C.D Block

A.B Block

minutes

minutes

Speed 1

Speed 1

20
seconds

ON

OFF

OFF

0

4

8

ON

OFF

OFF

0

8

Compressor
and
outdoor fan

Indoor fan

D Block

Compressor
and
outdoor fan

Indoor fan

C Block

Compressor
and
outdoor fan

Indoor fan

B Block

Compressor
and
outdoor fan

Indoor fan

A Block

20 seconds

20 seconds

minutes

minutes

Start

Temperature check

Start

Temperature check

Operation block decision

20 seconds

minutes

minutes

Start

Temperature check

Temperature check

Operation block decision

Start

Speed 1

Speed 1

OFF

OFF

0

8

ON

OFF

OFF

0

3

8

Speed 1

Speed 1

Running time

Running start ~ 1 hour

1~2 hours

2 hours ~

Set temperature compensation

Set temperature +0.5

Set temperature +1.0

Set temperature +1.5

(4)

ECONO Operation ( “ECONO” button on the remote controller : ON)

The set temperature changes as shown at right, and the

indoor unit fan speed is set on speed 2 .