![background image](/i/mitsubishi-heavy-industries/114433/mitsubishi-heavy-industries-srk-src-28hd-s-28hd-s/h/mitsubishi-heavy-industries-srk-src-28hd-s-28hd-s-006.png)
-
4
-
Model SRK40HD-S (Indoor unit)
SRC40HD-S (Outdoor unit)
Item
Model
SRK40HD-S
SRC40HD-S
Cooling capacity
(1)
W
3600
Heating capacity
(1)
W
4000
Power source
1 Phase, 220/230/240V, 50Hz
Cooling input
kW
1.12
Running current (Cooling)
A
5.3/5.1/4.9
Heating input
kW
1.16
Running current (Heating)
A
5.5/5.3/5.1
Inrush current
A
25.2
COP
Cooling: 3.21 Heating: 3.42
Cooling
sound level
Hi 40, Me 38, Lo 34
49
Noise level
Power level
dB
56
63
Heating
sound level
Hi 41, Me 38, Lo 34
50
Power level
57
64
Exterior dimensions
Height
×
Width
×
Depth
mm
250
×
815
×
249
640
×
850
×
290
Color
Cool white
Stucco white
Net weight
kg
9.0
41
Refrigerant equipment
Compressor type & Q’ty
–
5KS150DBB [Rotary type]
×
1
Motor
kW
–
1.1
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Refrigerant control
Capillary tubes + Electronic expansion valve
Refrigerant
(3)
kg
R410A
1.17 (Pre-Charged up to the piping length of 15m)
Refrigerant oil
R
0.43 (RB68A)
Deice control
MC control
Air handling equipment
Fan type & Q’ty
Tangential fan
×
1
Propeller fan
×
1
Motor
W
14
35
(Cooling)
9.0
38
Air flow (at High)
(Heating)
CMM
9.5
38
Air filter, Q’ty
Polypropylene net (washable)
×
2
–
Shock & vibration absorber
–
Cushion rubber (for compressor)
Electric heater
–
–
Operation control
Operation switch
Wireless-Remote controller
–
Room temperature control
MC. Thermostat
–
Pilot lamp
RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D
mm (in)
Liquid line:
φ
6.35 (1/4
″
)
Gas line:
φ
12.7 (1/2
″
)
Connecting method
Flare connecting
Attached length of piping
Liquid line: 0.4 m
Gas line : 0.33 m
–
Insulation
Necessary (Both sides)
Drain hose
Connectable
Power source cord
2.5 m (3 cores with Earth)
Size
×
Core number
1.5 mm
2
×
4 cores (Including earth cable)
Connection wiring
Connecting method
Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
Optional parts
–
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27ºC
19ºC
35ºC
24ºC
ISO-T1, JIS C9612
Heating
20ºC
–
7ºC
6ºC
ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even in the short piping.)
Operation data
(1)
Refrigerant
piping
Compressor: Overheat protection, overcurrent protection, Serial signal error protection, Indoor fan
motor error protection, Frost protection
The piping length is 7.5m.